A 12 V circuit with a 36 W load at the end of a 50 ft run of 14 AWG copper loses about 0.76 V. The chart compares this example by cable length and gauge.
Calculate voltage drop for your run →A 12 V LED landscape lighting run with a 36 W load at the end of 50 ft of 14 AWG copper loses an estimated 0.76 V. That leaves about 11.24 V at the far end in this simplified calculation. Changing the wire gauge, load or one-way distance changes the result. Compare the estimated voltage with the input range published for the fixture and driver.

Compare 16, 14 and 12 AWG copper
This chart assumes a nominal 12 V source, 36 W of fixture load, 3 A estimated current and the entire load at the end of a two-conductor copper run. Measure the actual cable route in one direction. The calculation doubles that distance to include the return conductor. Values below are voltage lost in the cable, rounded to two decimals.
| One-way run | 16 AWG | 14 AWG | 12 AWG |
|---|---|---|---|
| 25 ft | 0.60 V | 0.38 V | 0.24 V |
| 50 ft | 1.21 V | 0.76 V | 0.48 V |
| 75 ft | 1.81 V | 1.14 V | 0.72 V |
| 100 ft | 2.41 V | 1.52 V | 0.95 V |
The comparison uses copper resistance values of 4.02, 2.53 and 1.59 Ω per 1,000 ft for 16, 14 and 12 AWG respectively. The numbers estimate cable loss for the stated load. Select cable and equipment using their current, voltage, environmental and installation ratings.
Apply the chart to a 50 ft path
Six 6 W fixtures draw a combined 36 W. At 12 V, divide 36 W by 12 V for an estimated 3 A. For 50 ft of 14 AWG copper, the calculation is:
Voltage drop = 2 × 50 ft × 3 A × 2.53 Ω per 1,000 ft ÷ 1,000 = 0.759 V.
Subtract 0.759 V from the 12 V supply for an estimated far-end voltage of 11.24 V. The drop is about 6.3% of the nominal supply. If the model's voltage range is narrow, include room for variation in the supply, driver behavior and cable temperature when assessing the circuit.
For a different cable run, enter your fixture count, per-fixture wattage, one-way distance and copper gauge. The tool also estimates a transformer planning capacity. Open the voltage drop calculator.
Account for fixtures spaced along a run
The chart puts every fixture at the far end. When fixtures are tapped along a path, the current falls after each tap because downstream sections carry only the loads beyond them. Estimate loss section by section, then add the section drops along the path you are checking.
For example, place an 18 W group at 50 ft and another 18 W group at 100 ft on a 12 V, 14 AWG run. Using the nominal-voltage current estimate, the first 50 ft carries about 3 A and loses 0.76 V. The second segment carries about 1.5 A and loses another 0.38 V. The total estimated drop at the second group is about 1.14 V. The end-loaded chart estimates 1.52 V with the same total load at 100 ft.
For separate branches, map the common supply segments and the loads that each segment carries. A shared feed carries the sum of its downstream branch currents. Each branch then has its own drop and far-end voltage.
Check the fixture and transformer ratings before ordering
- Read the fixture nameplate and instructions for input voltage and AC or DC compatibility. Use the manufacturer's permitted operating range when reviewing the estimated voltage.
- Check the transformer's permitted loading and per-output or per-circuit limits. A capacity estimate alone does not resolve an excessive wire drop.
- Compare a shorter run, an adequately rated lower-resistance cable or a branch from the source. Compare 24 V only where the source, fixtures and controls support it. At the same 36 W load, nominal current at 24 V is 1.5 A, so the same cable has about half the estimated drop in volts.
- Have the installer check voltage under operating load at the relevant fixture terminals. When the run has several branches, check the far end of each branch and any near fixture that could see a higher voltage.
Use the broader outdoor LED guide when comparing fixture exposure, optics and controls. Outdoor LED Lighting Guide.
Prepare a fixture and transformer inquiry
Record the circuit voltage and output type, cable gauge, one-way length of each section and the fixture wattage at each tap. Include the mounting location and exposure conditions for the fixtures. If you have an existing transformer, include its model and ratings so the supplier can check the fixture and power requirements together. Send the circuit and fixture requirements to Tonghua Lighting.