IES Recommended Light Levels: Lux and Foot-Candles
The Illuminating Engineering Society (IES) recommends light levels by task and measurement plane. Light level, or illuminance, is how much light reaches a surface per unit area. A reading desk and a warehouse shelf face can need different targets. Use the tables below to compare planning ranges in lux and foot-candles. For a project target, look up the applicable guidance in the IES Lighting Library.
How to find and apply an IES light level
- Look up the task. Search by task or space in IES Lens, then filter to illuminance tables. IES Lens includes the lookup features of the Illuminance Selector. Open the source standard and confirm its edition, target illuminance and uniformity criteria. Full standards may require a subscription or a document lease.
- Use the specified measurement plane. Measure at the working surface, such as horizontally across a desk or vertically on a shelf face. A reading taken at the floor does not tell you how much light reaches a desk.
- Check the average and the low spots. Follow the measurement grid or method in the project guidance. An average across the grid can meet the target while individual points remain dim. Read any minimum and uniformity criteria separately, and use the maintained target when the design accounts for light loss over time.
Worked example: What does 300 lux mean?
If a 20 m² work plane averages 300 lux (about 27.9 foot-candles), roughly 6,000 lumens reach that plane: 300 × 20. This is an illustrative calculation. Use the lumen method to allow for light loss when estimating fixture output. The lighting layout calculator gives a starting count and spacing with its planning targets. Confirm the project target against the standard and check the layout with the selected fixtures’ photometric data.
Commercial Spaces
Planning values for office and commercial tasks. Check the working plane and the task-specific criteria for the project.
| Space Type | Foot-candles (fc, approx.) | Lux (lx) | Task Type |
|---|---|---|---|
| Office - Open Plan | 27.9–37.2 | 300-400 | Computer work |
| Office - Private | 27.9–46.5 | 300-500 | Reading, writing |
| Conference Room | 27.9–46.5 | 300-500 | Meetings |
| Lobby / Reception | 9.3–18.6 | 100-200 | Transient |
| Corridor | 4.6–9.3 | 50-100 | Circulation |
| Restroom | 9.3–18.6 | 100-200 | Grooming |
| Stairway | 4.6–9.3 | 50-100 | Safety |
| Retail - General | 27.9–46.5 | 300-500 | Merchandise |
| Retail - Feature Display | 92.9–185.8 | 1000-2000 | Accent |
| Restaurant - Dining | 4.6–9.3 | 50-100 | Dining |
| Restaurant - Kitchen | 46.5–92.9 | 500-1000 | Food prep |
| Hotel Lobby | 9.3–13.9 | 100-150 | Transient |
| Bank Teller | 46.5–69.7 | 500-750 | Transaction |
Industrial & Warehouse
Industrial tasks vary widely. Check the detail, contrast, safety needs, and age of occupants when selecting a target.
| Space Type | Foot-candles (fc, approx.) | Lux (lx) | Task Type |
|---|---|---|---|
| Warehouse - Bulk Storage | 9.3 | 100 | Bulk storage |
| Warehouse - Active Storage | 13.9–18.6 | 150-200 | Active storage |
| Warehouse - Order Picking | 18.6–27.9 | 200-300 | Picking, labeling |
| Factory - Rough Assembly | 9.3–18.6 | 100-200 | Large parts |
| Factory - Medium Assembly | 18.6–46.5 | 200-500 | Medium parts |
| Factory - Fine Assembly | 46.5–92.9 | 500-1000 | Precision |
| Factory - Inspection | 46.5–185.8 | 500-2000 | Quality control |
| Machine Shop | 27.9–46.5 | 300-500 | Machining |
| Loading Dock | 9.3–18.6 | 100-200 | Loading |
| Welding Area | 27.9–46.5 | 300-500 | Welding |
| Cold Storage | 13.9–18.6 | 150-200 | Storage, picking |
Residential
Starting values for residential spaces. Assess reading, cooking, and other task areas separately from general room lighting.
| Space Type | Foot-candles (fc, approx.) | Lux (lx) | Task Type |
|---|---|---|---|
| Living Room | 4.6–9.3 | 50-100 | General, social |
| Living Room - Reading | 18.6–27.9 | 200-300 | Reading |
| Kitchen - General | 27.9–37.2 | 300-400 | General |
| Kitchen - Counter | 46.5–69.7 | 500-750 | Food prep |
| Bathroom | 18.6–46.5 | 200-500 | Grooming |
| Bedroom | 4.6–9.3 | 50-100 | General |
| Bedroom - Reading | 18.6–27.9 | 200-300 | Reading |
| Home Office | 27.9–46.5 | 300-500 | Computer work |
| Dining Room | 9.3–18.6 | 100-200 | Dining |
| Garage | 9.3–18.6 | 100-200 | Storage, parking |
| Laundry Room | 18.6–27.9 | 200-300 | Laundry |
| Hallway | 4.6–9.3 | 50-100 | Circulation |
Outdoor & Site Lighting
Outdoor light levels depend on the site, traffic, surrounding brightness, and local requirements. Check glare and light spill as well as illuminance.
| Space Type | Foot-candles (fc, approx.) | Lux (lx) | Task Type |
|---|---|---|---|
| Parking Lot - Low Activity | 0.5–0.9 | 5-10 | Basic security |
| Parking Lot - High Activity | 0.9–1.9 | 10-20 | Shopping, event |
| Walkway / Sidewalk | 0.9–1.9 | 10-20 | Pedestrian |
| Street - Residential | 0.5–0.9 | 5-10 | Low speed road |
| Street - Commercial | 0.9–1.9 | 10-20 | Medium traffic |
| Building Entrance | 4.6–9.3 | 50-100 | Entry, security |
| Gas Station Canopy | 9.3–18.6 | 100-200 | Service area |
| Landscape - Accent | 0.5–1.9 | 5-20 | Decorative |
| Loading Area | 4.6–9.3 | 50-100 | Truck loading |
Healthcare Facilities
Healthcare tasks require specialist design criteria. These examples only support early discussions about room lighting. Consult the project requirements for examination and procedure lighting; the table does not cover surgical fields.
| Space Type | Foot-candles (fc, approx.) | Lux (lx) | Task Type |
|---|---|---|---|
| Patient Room | 9.3–18.6 | 100-200 | General, rest |
| Patient Room - Exam | 46.5–69.7 | 500-750 | Examination |
| Examination Room | 46.5–92.9 | 500-1000 | Medical exam |
| Laboratory | 46.5–92.9 | 500-1000 | Lab analysis |
| Pharmacy | 46.5–69.7 | 500-750 | Dispensing |
| Nurse Station | 27.9–46.5 | 300-500 | Charting, computer |
| Waiting Room | 9.3–18.6 | 100-200 | Waiting |
| Corridor | 4.6–9.3 | 50-100 | Circulation |
Educational Facilities
Check classroom tasks, screen use, glare, and the working plane when selecting educational lighting criteria.
| Space Type | Foot-candles (fc, approx.) | Lux (lx) | Task Type |
|---|---|---|---|
| Classroom - General | 27.9–46.5 | 300-500 | Reading, writing |
| Lecture Hall | 27.9–46.5 | 300-500 | Note-taking |
| Library - Reading Area | 27.9–46.5 | 300-500 | Reading |
| Library - Stacks | 18.6–27.9 | 200-300 | Browsing |
| Science Laboratory | 46.5–69.7 | 500-750 | Experiments |
| Art Classroom | 46.5–92.9 | 500-1000 | Art, color work |
| Computer Lab | 18.6–27.9 | 200-300 | Computer work |
| Gymnasium | 18.6–27.9 | 200-300 | Physical education |
| Corridor | 4.6–9.3 | 50-100 | Circulation |
Frequently Asked Questions
What are IES recommended light levels?
IES publishes recommended maintained illuminance for specific visual tasks and measurement planes. Look up the task in the IES Lighting Library and check the specified height, average or minimum target, and uniformity criteria.
How do I convert foot-candles to lux?
One foot-candle (fc) is about 10.764 lux (lx). Multiply foot-candles by 10.764, or divide lux by 10.764. For example, 30 fc is about 323 lx.
What is the difference between maintained and initial illuminance?
Initial illuminance describes the level with new, clean fixtures. Maintained illuminance is the level the design is meant to deliver near the end of the maintenance cycle. Check whether the guidance specifies an average or a minimum on the task plane.
Which IES lighting standard should I use?
Start with the standard for the specific task and location, then confirm the edition cited by the project. Older materials may use IESNA, short for the Illuminating Engineering Society of North America. Consult the IES Lighting Library for the applicable document and check local requirements separately.
Related Calculators
Recessed Lighting Layout Calculator
Enter the room dimensions, mounting height, and fixture output to create a preliminary lighting grid. Compare fixture count and spacing, then check the layout against the selected fixture’s photometry.
LED Beam Angle Calculator
Enter the beam angle and distance to estimate the beam diameter on a surface. If you know the area to cover, use the reverse calculation to find a starting angle.
LED Color Temperature Selector
Compare warm, neutral, and cool white light for your room. Choose how the space is used, or limit the recommendations to 2700–3000K for a warmer appearance.